Efficient testing of current transformers with the CT Analyzer

Current transformer testing with the CT Analyzer on a current transformer in the high-voltage bushing of a 380kV power transformer. (Image source: OMICRON)

Berlin-based 50Hertz Transmission GmbH is responsible for operating, maintaining, planning, and expanding the 380/220kV transmission grid in the north and east of Germany

The company operates conventional current transformers at 380kV, 220kV, 110kV and 30kV as freely accessible units (in outdoor switchgear installations), bushing type on major systems (power transformers, compensation coils) and those incorporated in gas-insulated switchgear systems (GIS). 50Hertz Transmission has been exclusively using the CT Analyzer from OMICRON for its current transformer testing for three years.

The company?s policy states that a test of the current transformers, using the secondary-side testing method, is performed during commissioning, at stipulated intervals, after faults or if any unusual behaviour has been observed. This test should at least include a load measurement, insulation test and a check of all of the cores. Other current transformer data is also relevant from a technical perspective, including overcurrent limiting factor for measurement cores or the accuracy limiting factor and the determination of the accuracy class for protection cores.

The old approach to current transformer testing

With conventional testing devices, such as those used at 50Hertz Transmission up until 2008, high currents were generated, the current transformer was energised via the primary connections, and measurements were taken on the secondary side. This approach enabled the minimum requirements of testing at the secondary-side to be met.

It was not possible, however, to test the saturation characteristics of the current transformers or determine the overcurrent characteristic. As such, it was not possible to define their exact class.

Current transformer testing with the CT Analyzer

Today, 50Hertz Transmission uses the CT Analyzer from OMICRON for all of its current transformer testing. As well as the load measurement, various additional tests are performed on the protection and measurement cores. These include the measurement of the winding resistance, the magnetisation characteristic curve, the turns ratio, and the determination of the accuracy/overcurrent limiting factor. The results are documented in a test report for each current transformer core. This report is then made available in the company?s monitoring and maintenance system for further analysis and evaluation.

Practical experience

?Using the optimum test set-up increases measurement accuracy,? explained Mathias Mieth, process coupling specialist at 50Hertz Transmission. Practical tests and experience gained using the CT Analyzer have, for example, shown that measurements taken on the secondary side should generally use a four-wire measurement. Here, the secondary-side test cable and measurement cable are connected directly to the test object.

Parallel connection of the measurement and testing cables to the live terminals should also be minimised and contact resistance reduced (e.g. when connecting the primary-side measurement cable to fixed ball points).

?To avoid interference, we jumper all cores of the current transformer that are not included in the test or connect them on the secondary side,? Mieth added.

For current transformers in bushings, GIS systems, or those which do not allow connection of the measurement cable on the primary-side, 50Hertz Transmission performs a ?reduced current transformer test?. This includes a resistance measurement, a recording of the magnetisation characteristic curve (with knee point determination), and the determination of the indirect security factor and accuracy limiting factor.

CT Analyzer as reference

In existing GIS systems, 50Hertz Transmission currently uses split-core current transformers for 110kV cables, which are intended to supplement those in the GIS system. Since some of these transformers are also used for the accounting measurement, they need to be calibrated. In its Advanced Version (measurement up to class 0.1), the CT Analyzer serves as a reference testing unit for initial calibration or recalibration of these current transformers during onsite measurements.

Effective and practical

?With the CT Analyzer, we have a device that allows effective, low-cost, and practicable testing of current transformers,? Mieth noted. ?Another powerful argument is that additional functional modules can be integrated in to the CT Analyzer at any time.?